University of Wollongong
Browse

Impact of Multiple Grid-Connected Solar PV Inverters on Harmonics in the High-Frequency Range

journal contribution
posted on 2024-11-17, 14:56 authored by Kasun Peiris, Sean Elphick, Jason David, Duane Robinson
In recent years, integration of solar photovoltaic (PV) systems into distribution networks has been increasing rapidly, as it has become the most promising renewable energy source (RES) in the transition of power generation from centralised to decentralised systems. With the power electronic (PE) interfaces that use high-frequency internal switching, all renewable energy sources are considered to be harmonic emitters, especially near switching frequencies, i.e., above 2 kHz. This paper evaluates the behaviour of high-frequency harmonics in the 2–20 kHz range due to the parallel operation of multiple solar PV inverters connected to a low-voltage (LV) network. The circulation current component that flows within the installation due to the low impedance paths at higher frequencies is analysed. Summation of high-frequency harmonic currents is observed with phase diversity analysis. The circulating current component can become 14 times higher than the grid current component at higher frequencies.

Funding

Australian Government (GIL73697)