University of Wollongong
Browse

Sag testing of dairy farm milking equipment

Download (645.81 kB)
conference contribution
posted on 2024-11-13, 21:10 authored by Victor GosbellVictor Gosbell, Victor SmithVictor Smith, Duane RobinsonDuane Robinson, B S Perera
Sags are widely reported as being one of the worst power quality problems and are particularly common in rural areas. Automated milking equipment on dairy farms are thus very susceptible to malfunction by sags. In assessing the relative cost/benefits of sag mitigation in the dairy or the supply network it is important to know the dairy equipment immunity level. It is shown how a harmonic generator can be used to determine this information. Testing revealed that the motor contactor was a critical component as it was unable to ride through a 40% sag longer than about 0.5 seconds. The milking equipment without contactor gave unsatisfactory performance for 50% sags longer than 1 second and for interruptions exceeding 0.5 second.

History

Citation

This paper originally appeared as: Gosbell, VJ, Smith, V, Robinson, DA et al, Sag testing of dairy farm milking equipment, Proceedings. PowerCon 2000. International Conference on Power System Technology, 4-7 December 2000, vol 2, 947-952. Copyright IEEE 2000.