A modelling technique is developed for determining the harmonic voltage distribution across a distribution system when there is an equitable distribution of harmonic emission. The harmonic voltages at the 132kV and 415V levels are fixed to values based on IEC Compatibility and Planning Levels and the intermediate voltages determined. Studies are made of six systems, typical of Australian distribution practice, to examine the effect of choice of voltage level and system parameters over the harmonic range of 2-40. Based on the study, harmonic Planning Levels are recommended for application to Australian distribution systems.
History
Citation
V. J. Gosbell, V. W. Smith, D. A. Robinson & W. Miller, "Harmonic Planning Levels for Australian Distribution Systems," in AUPEC2003, 2003, pp. 49-1-49-6.