Allocation of equal harmonic emission rights to MV customers having the same maximum demand is a key concept in the new Australian harmonic standard AS/NZS 61000.3.6 [1]. Some difficulty can arise with the application of the standard when customers are spread out along a feeder with significantly different fault levels. One proposed method of overcoming this problem is to reduce the allocation as the square root of the fault level [2]. This method requires the calculation of an allocation constant that is applied to all customers connected to the same zone substation. This paper gives a methodology for calculating the harmonic allocation constant when there is incomplete data, and discusses some simplifying assumptions that can be made to optimise calculations.
History
Citation
D. A. Robinson, V. J. Gosbell & S. Perera, "Harmonic Allocation Constant for Implementation of AS/NZS 61000.3.6," in Proceedings of the Australasian Universities Power Engineering Conference AUPEC 2001, 2001, pp. 142-147.